    Rated power: 0.7-7MW


    Inlet/outlet water temperature: 80/60℃


    Radiant heating surface area: 5.54-28.8㎡


    Convection heating surface area: 16.1-187.44㎡

Shanghai MAC is a leading manufacturer and supplier of Vacuum hot water unit.

A Vacuum Hot Water Unit is an energy-efficient heating device that generates hot water via heat exchange in a sealed vacuum chamber. It uses diverse heat sources (natural gas, electricity, waste heat, etc.) to vaporize the heat transfer medium at low temperatures, which transfers heat to cold water through a heat exchanger before condensing for cyclic use. Boasting high thermal efficiency (92%-98%), safety (no explosion risk), stable temperature control, and a compact design, it’s widely applied in commercial (hotels, hospitals), industrial (process heating), and residential (centralized supply) scenarios for hot water and heating needs.

If you want to know more about our Vacuum hot water unit price, please feel free to contact us, we will reply you within 24 hours.

Technical Information of Vacuum Hot Water Unit:

 

Technical Parameters 

Parameter Range 

Description

Rated Thermal Power

0.7MW - 70MW (equivalent to 600,000 kcal/h - 12,000,000 kcal/h)

Small-sized units are suitable for commercial venues; units above 14MW can meet high-load demands such as centralized heating in residential areas and industrial process heating.

Operating Vacuum Degree

2 - 8kPa (absolute pressure)

Triggers vacuum pump pressure compensation or shutdown when below the threshold to prevent air from entering and affecting heat exchange efficiency; normal working pressure is mostly less than 0.7bar.

Thermal Efficiency

92% - 95% for conventional models, up to 103% for condensing models, and 105% - 107% for some imported models

Condensing models improve efficiency by recovering flue gas condensation heat, saving over 10% energy compared to ordinary models.

NOₓ Emission

≤30mg/Nm³ for conventional models, ≤15mg/Nm³ for ultra-low NOₓ models

Some models complying with environmental standards can achieve emissions as low as 28mg/Nm³, suitable for scenarios with strict environmental requirements.

User-Side Supply Water Temperature

40 - 60 for domestic hot water, 60 - 95 for heating

Some industrial models can reach an outlet water temperature of ≤110; temperature fluctuation is ≤±2, and ≤±0.5 for high-precision models.

Heat Transfer Fluid Temperature

40 - 90 under normal conditions; over-temperature alarm setpoint is mostly 98

The burner automatically shuts down and alarms when over-temperature occurs to avoid equipment damage.

Design Pressure

1.0MPa for conventional heat exchangers, 1.6 - 2.0MPa for pressure-resistant models

Although the unit operates under negative pressure, heat exchange components are designed according to pressure-bearing standards to ensure structural stability.

Operating Noise

≤65dB

Adopts silent fans and proportional combustion technology, suitable for noise-sensitive scenarios such as hospitals and office buildings.

Startup Heating Time

≤5 minutes

Tube bundle water-cooled furnace models heat up faster due to less heat transfer fluid volume.

Power Distribution

1.4kW - 75kW

Increases with the unit's power; for example, the power distribution of a 12,000,000 kcal/h model reaches 75kW, with a power supply of 380V/50Hz for most models.

Applicable Altitude

0 - 5000 meters

Some high-altitude adapted models can maintain 93% thermal efficiency at 3000 meters above sea level through adaptive combustion control.

Safety Protection Parameters

Burst pressure of explosion-proof valve diaphragm: 0.01MPa; over-pressure alarm setpoint: 5kPa

Equipped with multiple protections such as over-temperature, over-pressure, and abnormal water level; gas-fired models are equipped with gas leakage detection devices.

Packing of Vacuum Hot Water Unit:

 